Project: Pet food Emulsifier Control System Upgrade
Project Overview
- Site visit, operation walk through, discussion for revision on expectations for new system.
- New mechanical drawings provided and circuit schematics, inverter picked for operation of main drive, requirement good starting torque and low current at starting, new local 250A MCCB with adjustable protection settings max current, instantaneous and time settings.
- New cooling system for main control panel.
Challenge:
- Dated system 20+ years old, difficult to fault find due to missing trunking, mark ups, modifications.
- Spare parts more difficult to come by and down time due to failures of older equipment.
- Main MCB 400A in plant main switchboard subject to tripping as existing system starts main motor (132kW) by star / delta and is close to maximum starting time trip threshold.
- Temperature rise in main panel in summer in plant leads to overtemperature.
- No diagnostics assistance in trip conditions.
Solution:
- A brand-new custom-built stainless-steel enclosure, complete with 100mm sanitary stainless steel 316 air intake bottom and extract top for fresh cool air circulation to the enclosure which is IP65.
- Delta C2000+ variable frequency drive, lower harmonic solution, C/W EMC filter, reducing the starting current to 1.5xIn from the
previous 4-5xIn. - PLC and HMI, giving a diagnostic readout of all trip conditions.
- Brand new control components, MCCB door interlocked isolation, line contactors, overloads etc according to the customer specifications.
- New drawing set full electrical and mechanicals.
Features:
The new system sits around 1.44 metres off the ground on a stainless steel frame, the HMI at this point is approximately eye level off the ground at 1.82m which will flag a red flashing light at any fault condition on the home page, pushing the alarm light will take you to the faults page and indicate the fault condition in more details via the fault table.
Starting is now controlled by the drive current limit, the Delta C2000+ is able to start from 0.5Hz with full motor torque (open loop) keeping the starting current in the current limit and ramp the large main drive up to operational speed. The control panel is cooled by a constant flow of fresh filtered air and the new enclosure gives plenty of space for any additional future upgrades with spare capacity.